Provide one-stop intelligent power solutions for global customers.An air-insulated RMU (Ring Main Unit) is a medium-voltage switchgear that uses air as the primary insulation medium instead of SF6 gas or eco-gas mixtures. The RAYDAFON Dis Sub-12 places the busbar and insulated conductors in air rather than in a sealed gas tank — making it maintenance-friendly, fully recyclable at end-of-life, and free from gas leakage risk. It achieves 12kV dielectric strength through epoxy-insulated conductors and an optimized three-phase vertical layout, achieving a cabinet width of only 500mm — the most compact fixed air-insulated design available for box-type substations and ring network distribution systems.
The three-phase vertical layout stacks the three phase conductors vertically rather than side by side — a design that reduces cabinet width by up to 50% compared to conventional horizontal-layout switchgear. In a box-type substation or a containerized distribution room, this translates directly into more feeders per square meter and lower civil construction cost.
The vacuum interrupter structure is solid, with pressure relief channels both above and behind the cabinet. These channels direct arc products away from the operator zone in the event of internal arc fault, reducing the risk of internal combustion and ensuring the safety of personnel and property. The enclosure is maintainable throughout its service life.
No gas filling, no harmful gas emissions. The air-insulated design eliminates SF6 — a greenhouse gas with GWP 23,500 — and any eco-gas mixture. At end-of-life, all primary components can be separated and recycled without gas reclamation procedures.
Cabinet width is only 500mm, occupying less site area. Inlet and outlet cable installation height is ≥600mm. All conductors use hard connection for easy maintenance. Any combination of protection, control, and monitoring functions is fully integrated to meet distribution network automation requirements.
Six standard module types (C circuit breaker, F load switch + fuse, V vacuum circuit breaker, PT voltage transformer, M metering, D bus-tie) can be combined in any arrangement. Both above-ground and below-ground isolation are supported. See full RMU range →
| Item | Unit | Parameter |
|---|---|---|
| Rated Voltage (Ur) | kV | 12 |
| Rated Frequency (fr) | Hz | 50 |
| Rated Current (Ir) — Main | A | 1250 |
| Rated Current (Ir) — Fuse Circuit | A | 125* |
| Power Freq. Withstand — Phase-Earth | kV | 42 |
| Power Freq. Withstand — Isolated Fracture | kV | 48 |
| Lightning Impulse — Phase-Earth | kV | 75 |
| Lightning Impulse — Isolated Fracture | kV | 85 |
| Power Freq. Withstand — Auxiliary Circuit | kV | 2 |
| Short-Time Withstand — Main / Ground (4s) | kA | 31.5 |
| Short-Time Withstand — Earth Circuit (2s) | kA | 27.4 |
| Peak Withstand — Main / Ground | kA | 80 |
| Peak Withstand — Earth Circuit | kA | 68.5 |
| Short-Circuit Closing Current | kA | 80 (V) / 63 (C) |
| Short-Circuit Breaking Current | kA | 31.5 |
| Rated Transfer Current | A | 3150 |
| Operation Sequence | — | O-0.3s-CO-180s-CO |
| Short-Circuit Breaking Times | times | 30 |
| Mechanical Life — CB / Load Switch | ops | 10,000 |
| Mechanical Life — Three-Station Switch | ops | 5,000 |
| Enclosure Protection Grade | — | IP4X |
* Rated current of load switch + fuse combination depends on the high-voltage fuse selected. Rated short-circuit breaking current is limited by the high-voltage fuse.
For a complete air-insulated distribution solution, pair the Dis Sub-12 with:
Share your voltage rating, current rating, and module configuration — our engineers will reply with a tailored Dis Sub-12 configuration and factory-direct quote within 24 hours.